Part Number Hot Search : 
DS2172 GBJ15005 GBPC4008 CA3096M D0305 R3010T22 74AHCT14 CA3290AE
Product Description
Full Text Search
 

To Download B84143V0006R027 Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 EMC filters
3-line filters
Sine-wave output filters Rated current 6 to 35 A
Series/Type: Date: B84143V*R027 January 2006
EPCOS AG 2006. Reproduction, publication and dissemination of this data sheet and the information contained therein without EPCOS' prior express consent is prohibited.
3-line filters Sine-wave output filters
Sine-wave filters for 3-phase systems Rated voltage 440/250 V AC, 50/60 Hz Rated current 6 to 35 A Construction
3-line filter Metal case
B84143V*R027
Features

Easy to install
Space-saving design
Degree of protection: IP 201)
Motor cables of more than 100 m possible
Minimized motor noise and eddy current losses
in the motor windings
Applications
Sine-wave output filters for frequency converters in
- variable speed drivers - solar systems - UPS Terminals
Finger-safe terminal blocks
Marking Marking on component: Manufacturer's logo, ordering code, rated voltage, rated current, rated temperature, climatic category, date code, terminal assignment Minimum marking on packaging: Manufacturer's logo, ordering code Further versions
Higher currents for sine-wave output filters on request EMC sine-wave filters on request
1) To IEC 60529
Please read Cautions and warnings and
Important notes at the end of this document.
2
01/06
3-line filters Sine-wave output filters
Typical circuit diagram
Converter U1 V1 W1 Load U2 V2 W2
B84143V*R027
SSB1572-D-E
Technical data and measuring conditions Rated voltage VR Rated current IR Test voltage Vtest Overload capability (thermal) Converter output frequency fM Converter pulse frequency fP Voltage drop (input to output) V Capacitive reactive current Iq Max. voltage Vpeak (e.g. overshot pulse edge max.) Max. dv/dt at input Climatic category (IEC 60068-1) Characteristics and ordering codes VR AC V 440/250 IR A 6 12 16 25 35 Terminal Iq cross section A mm2 4 4 4 6 6 0.24 0.48 0.81 1.20 1.60 V V 10 8 8 7 7 3 Rtyp m 200 66 49 27 15 01/06
Approx. weight kg 5.2 7.9 8.3 11.1 16.6 Ordering code 440/250 V AC, 50/60 Hz Referred to 40 C ambient temperature 1770 V DC, 2 s (line/line) 2700 V DC, 2 s (lines/case) 1.5 * IR for 1 min per hour 0 ... 100 Hz 6 ... 16 kHz At IR and 50 Hz At 400/230 V AC, 50 Hz (typical value) 700 V 5 kV/s 25/100/21 (-25 C/+100 C/21 days damp heat test)
B84143V0006R027 B84143V0012R027 B84143V0016R027 B84143V0025R027 B84143V0035R027
Please read Cautions and warnings and
Important notes at the end of this document.
3-line filters Sine-wave output filters
Dimensional drawings B84143V0006R027 (6 A)
372 40 27.5 350
B84143V*R027
95
20 37.5 Thread M5
PE U2 V2 W2
54.5
45
380 3650.3
6.5
Terminal blocks 4 mm 2 Tightening torque 0.6 ... 0.8 Nm
B84143V0012R027, B84143V0016R027 (12 A, 16 A)
372 40 27.5 350 95
20 37.5 Thread M5
PE U2 V2 W2
89.5
80
380 3650.3
6.5
Terminal blocks 4 mm 2
Tightening torque 0.6 ... 0.8 Nm
Please read Cautions and warnings and
Important notes at the end of this document.
4
01/06
91
SSB1568-K-E
LOAD
Inverter
700.3
Marking
PE U1 V1 W1
115
91
SSB1567-C-E
LOAD
Inverter
700.3
Marking
PE U1 V1 W1
80
3-line filters Sine-wave output filters
B84143V0025R027 (25 A)
381 40 27.5 350
B84143V*R027
95
20 37.5 Thread M5
PE U2 V2 W2
104
114
380 3650.3
Terminal blocks 6 mm 2 Tightening torque 1.5 ... 1.8 Nm
B84143V0035R027 (35 A)
381 40 45 350 130
20
55 380 3650.3
6.5
Thread M5
104
114
PE U2 V2 W2
Terminal blocks 6 mm 2 Tightening torque 1.5 ... 1.8 Nm
Please read Cautions and warnings and
Important notes at the end of this document.
126
SSB1571-5-E
LOAD
Inverter
PE U1 V1 W1
5
01/06
1050.3
Marking
150
91
SSB1570-W-E
LOAD
Inverter
700.3
Marking
PE U1 V1 W1
6.5
150
EMC filters Cautions and warnings
Important information Please read all safety and warning notes carefully before installing the EMC filter and putting it into ). The same applies to the warning signs on the filter. Please ensure that the signs operation (see are not removed nor their legibility impaired by external influences. Death, serious bodily injury and substantial material damage to equipment may occur if the appro priate safety measures are not carried out or the warnings in the text are not observed. Using according to the terms The EMC filters may be used only for their intended application within the specified values in low voltage networks in compliance with the instructions given in the data sheets and the data book. The conditions at the place of application must comply with all specifications for the filter used. Warnings
It shall be ensured that only qualified persons (electricity specialists) are engaged on work such

as planning, assembly, installation, operation, repair and maintenance. They must be provided with the corresponding documentation. Danger of electric shock. EMC filters contain components that store an electric charge. Danger ous voltages can continue to exist at the filter terminals for longer than five minutes even after the power has been switched off. The protective earth connections shall be the first to be made when the EMC filter is installed and the last to be disconnected. Depending on the magnitude of the leakage currents, the particular specifications for making the protective-earth connection must be observed. Impermissible overloading of the EMC filter, such as impermissible voltages at higher frequen cies that may cause resonances etc. can lead to destruction of the filter housing. EMC filters must be protected in the application against impermissible exceeding of the rated currents by suitable overcurrent protective.
6
01/06
EMC filters Important notes
The following applies to all products named in this publication: 1. Some parts of this publication contain statements about the suitability of our products for certain areas of application. These statements are based on our knowledge of typical requirements that are often placed on our products in the areas of application concerned. We nevertheless expressly point out that such statements cannot be regarded as binding statements about the suitability of our products for a particular customer application. As a rule, EPCOS is either unfamiliar with individual customer applications or less familiar with them than the customers themselves. For these reasons, it is always ultimately incumbent on the customer to check and decide whether an EPCOS product with the properties described in the product specification is suitable for use in a particular customer application. 2. We also point out that in individual cases, a malfunction of passive electronic components or failure before the end of their usual service life cannot be completely ruled out in the current state of the art, even if they are operated as specified. In customer applications requiring a very high level of operational safety and especially in customer applications in which the malfunction or failure of a passive electronic component could endanger human life or health (e.g. in accident prevention or life-saving systems), it must therefore be ensured by means of suitable design of the customer application or other action taken by the customer (e.g. installation of protective circuitry or redundancy) that no injury or damage is sustained by third parties in the event of malfunction or failure of a passive electronic component. 3. The warnings, cautions and product-specific notes must be observed. 4. In order to satisfy certain technical requirements, some of the products described in this publication may contain substances subject to restrictions in certain jurisdictions (e.g. because they are classed as "hazardous"). Useful information on this will be found in our Material Data Sheets on the Internet (www.epcos.com/material). Should you have any more detailed questions, please contact our sales offices. 5. We constantly strive to improve our products. Consequently, the products described in this publication may change from time to time. The same is true of the corresponding product specifications. Please check therefore to what extent product descriptions and specifications contained in this publication are still applicable before or when you place an order. We also reserve the right to discontinue production and delivery of products. Consequently, we cannot guarantee that all products named in this publication will always be available. 6. Unless otherwise agreed in individual contracts, all orders are subject to the current version of the "General Terms of Delivery for Products and Services in the Electrical Industry" published by the German Electrical and Electronics Industry Association (ZVEI). 7. The trade names EPCOS, EPCOS-Jones, Baoke, CeraDiode, CSSP, MLSC, PhaseCap, PhaseMod, SIFI, SIKOREL, SilverCap, SIMID, SIOV, SIP5D, SIP5K, UltraCap, WindCap are trademarks registered or pending in Europe and in other countries. Further information will be found on the Internet at www.epcos.com/trademarks.
7
01/06


▲Up To Search▲   

 
Price & Availability of B84143V0006R027

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .